Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM01144
Parcel: 10714257E

Address:
16 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01144
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2014 MARTIN BROWN FIRE REVIEW Approved
03/11/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G-01; SHEET INDEX: THE INDEX INCLUDES A SHEET A-5.0. IT IS NOT IN THE SET. CLARIFY.
2. SHEET D-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE GENERAL NOTES.
3. SHEET A-2.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE GENERAL FLOOR PLAN NOTES.
4. SHEET A-2.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DETAIL NOTES.
5. SHEET A-2.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VCT SCHEDULE AND THE PAINT SCHEDULE.
6. SHEET A-3.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE CEILING NOTES.
7. SHEET A-4.0; SECTION 5 (A-A): A NOTE AT THE TOP OF THE WALL REFERENCES THE WALL AS 'EXISTING EXTERIOR LIGHT GAGE STUD WALL'. IS THIS A CMU WALL? VERIFY.
8. SHEET A-4.0; DETAIL 7: CALL OUT THE REINFORCING IN THE DETAIL.
9. SHEET A-4.0; DETAIL 9: AN ENLARGED DETAIL REFERENCE CALLS OUT 2/A4.0. IS THIS CORRECT? VERIFY.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/18/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM01144

1. Provide a 2012 IECC (interior) lighting calculation: use ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination.

Ken Van Karsen
Elect Plan Review
PDSD, City of Tucson
520-837-4912
03/24/2014 LHANLY1 WATER REVIEW Completed
03/24/2014 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Reqs Change PP M-2.0 The City of Tucson requires a minimum font size for 3/32" for upper and lower case letters. Revise specifications and general notes.

PP M-1.0 Keynote 3 references a 3/4" condensate line to be connected to lavatory tailpiece. Indicated line is 1". Clarify if connections from the two separate condensate lines are to connect, or run separately to separate lavatories. (or maybe just dump them into mop sink.

Bottom fed water heater requires vacuum relief valve per IPC 504.2.

Drain isometric on pp P1.0 appears to show a sanitary "tee" fitting at connection of mopsink drain to 2" drain from drinking fountain. This fitting needs to be a directional fitting.
03/24/2014 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Reqs Change PP M-2.0 The City of Tucson requires a minimum font size for 3/32" for upper and lower case letters. Revise specifications and general notes.

PP M-1.0 Keynote 3 references a 3/4" condensate line to be connected to lavatory tailpiece. Indicated line is 1". Clarify if connections from the two separate condensate lines are to connect, or run separately to separate lavatories. (or maybe just dump them into mop sink.

Bottom fed water heater requires vacuum relief valve per IPC 504.2.