Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T14CM01127
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Please indicate location of new and/or proposed fire hydrants on site plan. Refer to chapter 5 of the 2012 International Fire Code for spacing requirements. |
| 03/07/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Taco Bell - Old Vail Plaza T14CM01127 Building Plan (1st Review) TRANSMITTAL DATE: March 7, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Due to the site changes proposed a revised tentative plat is required. Contact Patricia Gehlen 520-837-4919 for submittal requirements. The tentative plan will need to be submitted and approved prior to a approval of the building plans. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 03/07/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | GENERAL 1. Provide an outline of required special inspections. 2. Provide the two part form for special inspectors certification. 3. Provide structural calculations for the following: a. All structural framing plans and details b. All foundation plans and details c. All suspended and roof top mounted HVAC equipment d. All foundations for pole mounted electrical fixtures 4. Provide a sub surface geo technical soils report. 5. Include sheet ADA1.1 in the site development package. 6. Provide an overall occupancy load calculation. END OF REVIEW |
| 03/07/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 03/18/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide tempered water for the lavatories in restrooms using approved devices conforming to ASSE 1070. The specified mixing valve by Lawler is not ASSE 1070 certified. Reference: Sections 416.5 and 607.1.2, IPC 2012. 2. Section 604.1, IPC 2012 allows water distribution systems to be designed using accepted engineering methods. Provide the source of the method used to determine the water demand (the total water demand, not just the cold water and the hot water demands) and size the water distribution system. 3. The developed length of the hot water supply piping appears to be greater than fifty feet from the water heater to the furthest hot water termination (a mixing valve); provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012. 4. Appliances (e.g. soda dispensers, ice makers, cheese melter, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 5. Clarify the purpose of installing a flow control device with a gravity grease interceptor. Reference: Sections 303.2 and 706.2, IPC 2012. 6. With reference to detail E/P2.0, a hub drain shall extend not less than 1" above the finished floor. Show how the floor around the hub drain is to be made impervious to water. Reference: Section 802.3.2, IPC 2012. 7. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Coordinate the plumbing plan with the waste and vent isometric. Reference: Section 905.4, IPC 2012. 8. Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Provide dimensions for the roof scuppers, overflow scuppers, and downspouts. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012. |
| 03/18/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1) Provide exterior lighting cut-sheets with sufficient data to determine compliance with the City of Tucson Outdoor Lighting code. Information to include lumen output, color temperature, and whether fixture is full cutoff. Keep in mind that on pp ES1.0 and E1.0 you are indicating that all fixtures are full cut-off. To use the allowed lumen calculations on pp E1.0 this will be necessary or you may use an alternate method for total lumens as per the OLC. |
| 03/18/2014 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of the water meter (the water meter is not shown on the civil utility drawing, C-04). Reference: Section 107.2.1, IBC 2012. 2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Verify that the location of the proposed backflow preventer is acceptable to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf |
| 03/20/2014 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 03/24/2014 The project has been reviewed and it can not be approved at this time. It appears that the proposed site layout is different from what was previously approved on the Tentative Plat (S07-156). The approved Tentative Plat may need to be revised. Contact Patricia Gehlen at 837-4919 for additional information. If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov Resubmittal Required: Revised Tentative Plat |
| 03/25/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations for the building envelope and the HVAC systems (e.g. COMcheck); use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope and the HVAC systems. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012. 2. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 4. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012. 5. Provide justification for not installing the split grill (C201) or the cheese melter (C250) under a Type I hood. Reference: Section 507.2.1, IMC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/26/2014 | CPIERCE1 | OUT TO CUSTOMER | Completed |