Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM01124
Parcel: 12501047B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01124
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. SHEET A2; ROOM FINISH SCHEDULE: IBC SECTION 1210.2.2 REQUIRES WALL MATERIALS IN TOILETS SHALL BE OF A TYPE THAT RESISTS MOISTURE EFFECTS. INCLUDE ON THIS SHEET A TYPE X GYP. BOARD AT THESE LOCATIONS.
02/26/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/27/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/27/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
02/27/2014 ROBERT SHERRY WATER REVIEW Approved
02/27/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
02/27/2014 LOREN MAKUS ENGINEERING REVIEW Approved
02/27/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The horizontal branch serving the common-vented lavatories requires a cleanout.
2. The hot water outlets for the lavatories shall be on the left and the cold water outlet on the right.
02/27/2014 MARTIN BROWN FIRE REVIEW Denied Need fire alarm system installed in building per IFC 907.2.2 #2
03/04/2014 CPIERCE1 WWM REVIEW Completed