Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM01124
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/26/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. SHEET A2; ROOM FINISH SCHEDULE: IBC SECTION 1210.2.2 REQUIRES WALL MATERIALS IN TOILETS SHALL BE OF A TYPE THAT RESISTS MOISTURE EFFECTS. INCLUDE ON THIS SHEET A TYPE X GYP. BOARD AT THESE LOCATIONS. |
02/26/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/27/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
02/27/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/27/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/27/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
02/27/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
02/27/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The horizontal branch serving the common-vented lavatories requires a cleanout. 2. The hot water outlets for the lavatories shall be on the left and the cold water outlet on the right. |
02/27/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Need fire alarm system installed in building per IFC 907.2.2 #2 |
03/04/2014 | CPIERCE1 | WWM | REVIEW | Completed |