| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 03/12/2014 | ANY | WWM | REVIEW | Active | |
| 03/12/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; the 4" fixture branch located downstream of the lavatories requires a 4" cleanout. [Initial comment: Provide cleanouts sized for the nominal size of pipes that they serve (i.e. provide a 4" cleanout for the 4" horizontal drain). Reference: Section 708.7, IPC 2012.] |
| 03/12/2014 | ROBERT SHERRY | WATER | REVIEW | Denied | Tucson Water limits a 5/8" water meter to a demand of 15 GPM. The demand for the fixtures in the Dollar Tree is 18 GPM. Contact Tucson water to obtain a larger water meter. [Initial comment: Provide the size of the existing water meter and its associated backflow preventer.] |