Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM01039
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/24/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/24/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/24/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/25/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/25/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1) Having bathroom exhaust fans connected to the occupancy sensor results in a violation of International Mechanical Code section 403.2.1. Provide a suitable sequence of operation for the exhaust fan and RTU4, or revise plans to omit supply air into the toilet rooms. |
| 02/25/2014 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the existing water meter and its associated backflow preventer. |
| 02/25/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 02/25/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide cleanouts sized for the nominal size of pipes that they serve (i.e. provide a 4" cleanout for the 4" horizontal drain). Reference: Section 708.7, IPC 2012. 2. According to the manufacturer, the specified temperature mixing valve is, "designed to be installed at a single outlet", it is not designed or listed to control the temperature of multiple fixtures. Reference: Sections 303.2, 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012. |
| 03/12/2014 | SPOWELL1 | WWM | REVIEW | Needs Review |