Permit Number: T14CM01039
Parcel: 106023040

Address:
3820 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01039
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
02/24/2014 LOREN MAKUS ENGINEERING REVIEW Approved
02/24/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/24/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/25/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/25/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1) Having bathroom exhaust fans connected to the occupancy sensor results in a violation of International Mechanical Code section 403.2.1. Provide a suitable sequence of operation for the exhaust fan and RTU4, or revise plans to omit supply air into the toilet rooms.
02/25/2014 ROBERT SHERRY WATER REVIEW Denied Provide the size of the existing water meter and its associated backflow preventer.
02/25/2014 KEN BROUILLETTE FIRE REVIEW Approved
02/25/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts sized for the nominal size of pipes that they serve (i.e. provide a 4" cleanout for the 4" horizontal drain). Reference: Section 708.7, IPC 2012.
2. According to the manufacturer, the specified temperature mixing valve is, "designed to be installed at a single outlet", it is not designed or listed to control the temperature of multiple fixtures. Reference: Sections 303.2, 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.
03/12/2014 SPOWELL1 WWM REVIEW Needs Review