Permit Number: T14CM01035
Parcel: 117131600

Address:
160 S SCOTT AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01035
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. The upstream cleanout shown in detail 205 is both incorrect and unnecessary; there is a proper cleanout 3-feet upstream of the backwater valve.Reference: Sections 708.3.5 and 708.5, IPC 2012.
03/07/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/10/2014 CARL SCHULTZ FIRE REVIEW Approved
03/13/2014 AROMERO4 WWM REVIEW Needs Review