Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM01035
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. The upstream cleanout shown in detail 205 is both incorrect and unnecessary; there is a proper cleanout 3-feet upstream of the backwater valve.Reference: Sections 708.3.5 and 708.5, IPC 2012. |
| 03/07/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/10/2014 | CARL SCHULTZ | FIRE | REVIEW | Approved | |
| 03/13/2014 | AROMERO4 | WWM | REVIEW | Needs Review |