Permit Number: T14CM01035
Parcel: 117131600

Address:
160 S SCOTT AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01035
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2014 STEVE SHIELDS ZONING REVIEW Approved
02/24/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the location of the exhaust discharge for EF-1 with regard to discharging outdoors, proximity to building openings and to property lines. Reference: Section 501.3.1, IMC 2012.
2. Provide structural details to show how the exhaust fan is to be connected to the building structure. Reference: Section 302.1, IMC 2012.
02/24/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
02/24/2014 ROBERT SHERRY WATER REVIEW Approved
02/24/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Completed
02/24/2014 JASON GREEN ENGINEERING REVIEW Approved
02/24/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the rim elevation of the next upstream sanitary manhole and the floor elevation for the revised restrooms. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
2. Clarify the direction of flow for the existing 4" S - it appears to flow to the north but the connection of the new building drain indicates that it flow to the south.
3. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
02/24/2014 KEN BROUILLETTE FIRE REVIEW Denied PLEASE UPDATE CODE REVIEW DATA ON SHEET T1.0
02/24/2014 LHANLY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/07/2014 SPOWELL1 WWM REVIEW Needs Review