Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM01035
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/24/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the location of the exhaust discharge for EF-1 with regard to discharging outdoors, proximity to building openings and to property lines. Reference: Section 501.3.1, IMC 2012. 2. Provide structural details to show how the exhaust fan is to be connected to the building structure. Reference: Section 302.1, IMC 2012. |
| 02/24/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 02/24/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/24/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 02/24/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/24/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the rim elevation of the next upstream sanitary manhole and the floor elevation for the revised restrooms. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. 2. Clarify the direction of flow for the existing 4" S - it appears to flow to the north but the connection of the new building drain indicates that it flow to the south. 3. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. |
| 02/24/2014 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PLEASE UPDATE CODE REVIEW DATA ON SHEET T1.0 |
| 02/24/2014 | LHANLY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/07/2014 | SPOWELL1 | WWM | REVIEW | Needs Review |