Permit Number: T14CM01031
Parcel: 12810069A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM01031
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/01/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/01/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. Revise the size of pipes and cleanouts shown in the waste and vent diagram, 1/P2.1. Cleanouts shall be sized per Section 708.7, IPC 2012 and any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited (e.g. see P-4, the back-to-back P-3 and P-2, and P-2A in the 1st floor women's restroom. Reference: Section 706.2, IPC 2012.
2. Comment not addressed. Correct the pressure drop due to static lift in the water pressure calculations
04/01/2014 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2014 SHANAE POWELL REJECT SHELF Completed