Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM01031
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/01/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/01/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. Revise the size of pipes and cleanouts shown in the waste and vent diagram, 1/P2.1. Cleanouts shall be sized per Section 708.7, IPC 2012 and any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited (e.g. see P-4, the back-to-back P-3 and P-2, and P-2A in the 1st floor women's restroom. Reference: Section 706.2, IPC 2012. 2. Comment not addressed. Correct the pressure drop due to static lift in the water pressure calculations |
| 04/01/2014 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/04/2014 | SHANAE POWELL | REJECT SHELF | Completed |