Permit Number: T14CM01031
Parcel: 12810069A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01031
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2014 KEN BROUILLETTE FIRE REVIEW Approved
03/06/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2.0; WALL TYPE 8: A NOTE INDICATES TO BRACE THE WALL FRAMING TO THE STRUCTURE ABOVE AT 48" O.C. PROVIDE A DETAIL ON THE DRAWINGS, INDICATING THE BRACING SIZE, HOW IT IS CONNECTED TO THE STRUCTURE ABOVE, AND HOW IT IS CONNECTED TO THE WALL. INCLUDE THE CONNECTOR SIZE AND QUANTITY.
2. SHEETS A2.0, A2.2, A3.0, A4.0, A5.0, A6.0, A6.1, A6.2, A7.0, A7.1, AND A8.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE LETTERING ON THESE SHEETS WHERE REQUIRED.
3. SHEET A2.0; WALL TYPES 4 AND 5: A NOTE INDICATES TO BRACE THE WALL FRAMING TO THE STRUCTURE ABOVE AT 48" O.C. PROVIDE A DETAIL ON THE DRAWINGS, INDICATING HOW THE FRAMING IS CONNECTED TO THE STRUCTURE. INCLUDE CONNECTOR SIZE AND QUANTITY.
4. SHEET A2.0: DARKEN THE LETTERING AT THE FINISH SCHEDULE AND THE LEGEND.
5. SHEET A2.0 (FIRST AND SECOND LEVEL REFERENCE PLANS); SHEET A6.0 (SECTION): CUT THIS SECTION ON THE PLANS.
6. SHEET A4.0; ROOF PLAN: TWO DETAILS CUT AT THE MECHANICAL SCREEN REFERENCE 12/A4.0 AND 12/A8.0. REVISE BOTH.
7. SHEET A6.0; SECTION: A DETAIL INDICATED IN THE MEETING ROOM REFERENCES 1/A8.0. IS THIS CORRECT?
8. SHEET A6.1; SECTION 4: TWO DIFFERENT SECTIONS ARE REFERENCED AS '4' IN THE TITLE. REVISE.
9. SHEET A6.2; COUNTERS AT SINKS: AT LEAST ONE SINK AND COUNTER NEEDS TO BE ACCESSIBLE PER THE IBC SECTION 1109.3. REVISE TO A 2'-10" COUNTER HEIGHT.
10. SHEET A8.0; SECTIONS 6 AND 7: THESE SECTIONS ARE TITLED AS 'SILL'. IS THAT CORRECT?
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/11/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
03/21/2014 ROBERT SHERRY WATER REVIEW Denied Provide a site drawing showing the route of the new building water service along with the location of both the new water meter and the new reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2012.
03/21/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size of pipes and cleanouts shown in the waste and vent diagram, 1/P2.1. Cleanouts shall be sized per Section 708.7, IPC 2012 and any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited (e.g. see P-4, the back-to-back P-3 and P-2, and P-2A in the 1st floor women's restroom. Reference: Section 706.2, IPC 2012.
2. Correct the pressure drop due to static lift in the water pressure calculations.
03/21/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2012.
2. Demonstrate energy code compliance for the alterations to the building envelope (e.g. exterior wall and window revisions) based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, and C402, International Energy Conservation Code 2012.
3. With the exception of AC-2, all of the packaged AC units are scheduled to have less than 25% outside air but a note on the Rooftop Packaged Gas Electric Air Conditioning Unit Schedule calls for the units to be equipped with 25-50% outside air dampers. Show how the HVAC controls are capable of reducing the outside air to the minimum flow rates required by Chapter 4, IMC 2012. Reference: Section C403.2.5, IECC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2014 CPIERCE1 REJECT SHELF Completed