Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM01014
Parcel: 140192770

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM01014
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/28/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The outside air duct for MS2 is not noted on the drawings. [Second comment: Provide calculations to show that the proposed 4" ducts are capable of supplying the required outside air to the indoor units.] [Initial comment: Show how outside air will be introduced into the inside HVAC units and provide the manufacturer's equipment data and installation instructions that support the proposed method of introducing outside air into the inside HVAC units. Reference: Sections 301 and 304.1, IMC 2012.]
2. Correct the arithmetic in the ventilation calculations for MS1. Clarify why room #4 ("MTG") is classified as an office and not as a conference room. [Second comment: The City of Tucson has adopted the 2012 IMC for calculating ventilation requirements, not ASHRAE 62.1-2007. Provide calculations per Section 403.3, IMC 2012.] [Initial comment: Revise the ventilation calculations using appropriate occupancy types (e.g. "coin-op laundry" instead of corridors and utilities; "conference room" instead of office, "hotel, multi-purpose" instead of lecture classroom, etc.). Do not truncate "fractional people" in the calculations, use equation 4-1 (Section 403.3.1.1, IMC 2012) to determine the breathing zone outdoor air flow, and follow the instructions in Sections 403.3.2.3 through 403.3.2.3.4, IMC 2012 for determining the ventilation for HVAC system MS-1. Reference: Section 403.2, IMC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
04/17/2014 AROMERO4 APPROVAL SHELF Completed
04/17/2014 AROMERO4 OUT TO CUSTOMER Completed
04/17/2014 AROMERO4 REJECT SHELF Completed