Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM01005
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | Cannot find the response to the previous requirement of: Per Appendix B of the 2012 International Fire Code, a residence of this size requires a fire flow of 2000 GPM out of the nearest hydrant, or the installation of fire sprinklers. Owner can a have a fire sprinkler company perform a flow test to determine if the water suply is adequate (and add data to cover sheet), or add note to plans to indicate intent to install fire sprinklers. |
| 03/26/2015 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Completed |