Permit Number: T14CM00955
Parcel: 12709016A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00955
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
02/19/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the mechanical design as required to avoid using the corridorsas return air ducts. Reference: Section 601.2, IMC 2012.
2. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
02/19/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
02/19/2014 ROBERT SHERRY WATER REVIEW Approved
02/19/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/19/2014 JASON GREEN ENGINEERING REVIEW Approved
02/19/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the support details for the water heater and provide calculations showing that it is safely supported.
02/19/2014 MARTIN BROWN FIRE REVIEW Approved
02/19/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/21/2014 CPIERCE1 WWM REVIEW Completed