Permit Number: T14CM00915
Parcel: 13624450A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00915
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
02/18/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012.
02/18/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
02/18/2014 ROBERT SHERRY WATER REVIEW Denied Provide the size of the existing water meter and the new total water demand.
02/18/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/18/2014 LAITH ALSHAMI ENGINEERING REVIEW Approved
02/18/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The specified mixing valve (Powers model LM490) conforms to ASSE 1017; provide tempered water for the lavatories in the restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
02/18/2014 KEN BROUILLETTE FIRE REVIEW Approved
02/18/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/19/2014 FRODRIG2 WWM REVIEW Completed