Permit Number: T14CM00889
Parcel: 125101360

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM00889
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please provide structural foundation and structural framing key plans in the calculations.
2. At detail 17/A0.2, the mounting height to the bottom of the main sign to the finished grade is to be 7'-0" not 7'-5" to the top of the sign nor 5'-0" to the bottom of sign. Please reconcil all these different mounting heights on this detail and resubmit.
3. At details A and B/A1.0, both Floor Plans, the lavatory is encroaching the water closet clearance area. As per ICC A117.1, Section 604.3.3, no other fixtures shall be within the required water closet clearance.
END OF REVIEW
03/20/2014 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Completed
03/20/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
03/20/2014 MARTIN BROWN FIRE REVIEW Approved
03/20/2014 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Completed
03/20/2014 LHANLY1 WATER REVIEW Completed
03/21/2014 DAVID RIVERA ZONING REVIEW Approved
03/21/2014 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/27/2014 CPIERCE1 REJECT SHELF Completed