Permit Number: T14CM00845
Parcel: 135057090

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00845
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2014 DAVID RIVERA ZONING REVIEW Approved
02/12/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Note #8 of the Hood/Exhaust fan schedule calls for O" clearance to combustibles. Clarify which portion of the hood will have this property (e.g. back, sides, top). Reference: Section 507.9, IMC 2012.
02/12/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
02/12/2014 ROBERT SHERRY WATER REVIEW Approved
02/12/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/12/2014 JASON GREEN ENGINEERING REVIEW Approved
02/12/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The dump sink shall be directly-connected to the grease waste drain system. Reference: section 802.1, IPC 2012.
2. The indirect waste lines from the expresso machine (605) and the ice bin (609) shall run independently to the indirect waste receptor to protect against cross-contamination or fouling. Reference: Section 801.2, IPC 2012.
02/12/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/13/2014 KEN BROUILLETTE FIRE REVIEW Approved
03/12/2014 GERRY KOZIOL WWM REVIEW Approved