Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM00845
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 02/12/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Note #8 of the Hood/Exhaust fan schedule calls for O" clearance to combustibles. Clarify which portion of the hood will have this property (e.g. back, sides, top). Reference: Section 507.9, IMC 2012. |
| 02/12/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 02/12/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/12/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/12/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/12/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The dump sink shall be directly-connected to the grease waste drain system. Reference: section 802.1, IPC 2012. 2. The indirect waste lines from the expresso machine (605) and the ice bin (609) shall run independently to the indirect waste receptor to protect against cross-contamination or fouling. Reference: Section 801.2, IPC 2012. |
| 02/12/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/13/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/12/2014 | GERRY KOZIOL | WWM | REVIEW | Approved |