Permit Number: T14CM00825
Parcel: 13507330G

Address:
7510 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM00825
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2014 STEVE SHIELDS ZONING REVIEW Approved
04/10/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/23/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/23/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change According to detail 6/A-8, the top of the water heater shelf will b 6'- 0" above the floor. The closet has a 7'- 0" high door which leaves an opening of just 12-inches above the water heater shelf. Removal of a 20.5" diameter water heater through this opening will be difficult. In addition, the specified water heater is 54.875" tall which means that the top of the water heater will be approximately at the same level as the bottom of the roof deck, leaving no room for piping or the batt insulation (if the water heater manages to miss the wide flanges supporting the roof). Coordinate the installation of the water heater with the architect to allow for maintenance access. [Initial comment: Clarify how the specified water heater will be able to be maintained or replaced in the mop closet. Reference: Sections 501.4 and 502.5, IPC 2012.]
04/30/2014 LAITH ALSHAMI ENGINEERING REVIEW Approved
05/05/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed