Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM00825
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/13/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Circle K - Expansion - 7510 E. 22nd Street T14CM00825 Building Plan (1st Review) TRANSMITTAL DATE: February 13, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans but cannot approve until a development package has been approved for the site changes 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 02/20/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A-2; FLOOR PLAN KEYNOTES (NOTES 8 AND 9): A REFERENCE FOR THE CABINET/COUNTER DETAILS IS LISTED AS SHEET A-7. REVISE THE SHEET NUMBER. 2. SHEET A-2; FLOOR PLAN KEYNOTES (NOTES 8 AND 10): A REFERENCE FOR THE EQUIPMENT PLAN IS LISTED AS SHEET A-3. REVISE THE SHEET NUMBER. 3. SHEET A-2; FLOOR PLAN KEYNOTES (NOTE 12): A REFERENCE FOR THE SPECIFICATIONS IS LISTED AS SHEET A-3. REVISE THE SHEET NUMBER. 4. SHEET A-2; FLOOR PLAN KEYNOTES (NOTE 15): A REFERENCE FOR THE WATER HEATER IS LISTED AS DETAIL 6/A-5. REVISE THE DETAIL NUMBER. 5. SHEET A-2; FLOOR PLAN KEYNOTES (NOTE 16): A REFERENCE FOR THE BACKFLOW PREVENTION DEVICE IS LISTED AS DETAIL 7/A-5. REVISE THE DETAIL NUMBER. 6. SHEET A-2; FLOOR PLAN KEYNOTES (NOTE 17): A REFERENCE FOR THE RESTROOM FIXTURES, HARDWARE, NOTES AND DETAILS IS LISTED AS SHEET A-8. REVISE THE SHEET NUMBER. 7. SHEET A-2; FLOOR PLAN KEYNOTES (NOTE 23): PROVIDE DIMENSIONS ON THE FLOOR PLAN FOR THE WIDTH OF THE NEW CONCRETE SIDEWALK ON THE SOUTHWEST END OF THE BUILDING. 8. SHEET A-2; FLOOR PLAN: THE INTERIOR DETAIL CUTS ALL REFERENCE SHEET A-5. REVISE THE DETAIL/SHEET NUMBERS. 9. SHEETS A-2 AND A-3; FLOOR PLAN: THE INTERIOR ELEVATION INDICATOR REFERENCES A, B, C, AND D ON SHEET A-3. REVISE THE ELEVATION AND SHEET NUMBER. 10. SHEET A-3; DOOR AND HARDWARE SCHEDULE: THE SECTION CUTS REFERENCE 9 AND 10 ON SHEET A-5. REVISE THE SECTION AND SHEET NUMBERS. 11. SHEET A-5; REFLECTED CEILING PLAN: THE INTERIOR DETAIL CUT REFERENCES SHEET A-5. REVISE THE DETAIL AND SHEET NUMBER. 12. SHEET A-7; TYPICAL C.M.U. WALL SECTION: THE MASONRY WALL VERTICALS ARE CALLED OUT AS #4 AT 48" O.C. VERIFY THIS MATCHES THE STRUCTURAL DRAWINGS. 13. SHEET A-8; DETAIL 4: ADD A NOTE TO THE DIAGONAL BRACE TO REFERENCE DETAIL 2/A-8 FOR THE CONNECTION AT THE STRUCTURE ABOVE. 14. SHEET A-8; DETAIL 6: THE DETAIL INDICATES A NEW METAL STUD WALL ADDED TO AN EXTERIOR C.M.U. WALL. THE PLAN DOES NOT INDICATE A NEW METAL STUD WALL AT THE C.M.U. WALL (INTERIOR). CLARIFY. 15. SHEET SN1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE GENERAL NOTES. 16. SHEET S1; FOUNDATION AND ROOF FRAMING PLANS: ADD NORTH ARROWS AND BUILDING GRID LINES TO THE PLANS TO MATCH THE ARCHITECTURAL. 17. SHEET S1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS: PROVIDE CALCULATIONS FOR THE 4'-0" SQUARE FOOTING INDICATED ON THE PLAN AT A 'POINT SUPPORT'. 18. SHEET S1; FOUNDATION PLAN: INDICATE THE NEW COLUMN SIZE AT THE NORTHWEST CORNER OF THE BUILDING. 19. SHEET S1; FOUNDATION PLAN: PROVIDE A DETAIL ON THE PLANS FOR THE INTERSECTION OF THE NEW WALL FOOTING AND THE EXISTING CANOPY FOOTING. 20. SHEET S1; FOUNDATION PLAN: PROVIDE A PLAN NOTE OR ADD A NEW DETAIL INDICATING THE DIFFERENCE BETWEEN A 'NEW FULL HEIGHT C.M.U. WALL' AND A 'LOW WALL'. 21. SHEET S1; ROOF FRAMING PLAN: CLEAR UP THE VERBIAGE FOR THE NEW COLUMN IN THE EXTERIOR WALL (TS 5X4). 22. SHEET S1 (FOUNDATION PLAN); SHEET S2 (DETAIL 3): THE PLAN (AND CALCULATIONS) INDICATE A 5'-0" SQUARE FOOTING, WHILE THE DETAIL INDICATES A 4'-0" FOOTING DIMENSION. CLARIFY. 23. SHEET S2; DETAIL 6: INDICATE ON THIS DETAIL HOW THE MANSARD STRUCTURE TIES INTO THE W14. 24. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/27/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. One line diagram has 2 new panels labeled A1 & B1; Site plan has new panels B1 & B2; Power floor plan has new panels B1 & C1. Coordinate all sheets. 2. Power plan has new circuitry to panel C, clarify. 3. Panel schedule A1 is not coordinated with power floor plan. Coordinate all circuits (relocated coolers are an issue). 4. Keynote 36 pp E2 has restroom exhaust fan connected to switch. This arrangement results in a violation of International Mechanical Code section 403.2.1. Place exhaust fan on a programmable timer to run whenever building is occupied, or interconnect with AH-2 to provide proper sequence of operation. |
| 03/10/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the identities of the indoor heat pump units - both AH-2? 2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan shall run as long as the HVAC system delivers air into the room). Reference: Section 403.2.1 (4), IMC 2012. |
| 03/10/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the Plumbing Fixture Schedule to reference sheet A-4 instead of sheet A-3 for the manufacturer and model number of the fixtures and appliances. 2. Clarify how the specified water heater will be able to be maintained or replaced in the mop closet. Reference: Sections 501.4 and 502.5, IPC 2012. 3. The specified backflow prevention device, Watts model 9BD, is not listed for ASSE 1022 as required for coffee machines or non-carbonated beverage dispensers. (In addition, detail 7/A-8 specifies the use of Watts model SD-3 dual check valves with atmospheric port & strainer for the non-carbonated beverage equipment.) Reference: Section 608.16.10, IPC 2012. 4. Provide a direct connection for the public hand washing sink. Reference: Sections 301.3 and 802.1, IPC 2012. 5. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 6. Show how the flow control device for the hydromechanical grease interceptor is to be installed below the floor level and in accordance with the manufacturer's instructions. Reference: Section 1003.4.2, IPC 2012. |
| 03/10/2014 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 03/10/2014, The plan can not be approved until the the Development Package is approved. |
| 03/10/2014 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/12/2014 | CPIERCE1 | REJECT SHELF | Completed |