Permit Number: T14CM00822
Parcel: 117067140

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00822
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
03/03/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 1: 1. SHEET TS1: EACH OF THE FOUR SUITES WILL REQUIRE A SEPARATE PERMIT. PROVIDE A SQUARE FOOTAGE FOR EACH SUITE (TOTAL 3527 SF) ON THE DRAWINGS. NO OCCUPANCY LOAD WILL BE REQUIRED UNTIL THE FIRST TENANT MOVES IN AND APPLIES FOR A C OF O OR TI.
2. PROVIDE A HIGH/LOW DRINKING FOUNTAIN AS REQUIRED BY CHAPTER 29 OF THE IBC, OR A POINT-OF-USE DISPENSER. INDICATE ON THE PLAN.
03/07/2014 KEN BROUILLETTE FIRE REVIEW Approved
03/07/2014 FRODRIG2 MECHANICAL-COMMERCIAL REVIEW Needs Review