Permit Number: T14CM00818
Parcel: 11451137D

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T14CM00818
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2014 MARTIN BROWN FIRE REVIEW Denied Change project summary to reflect compliance with 2012 International Fire Code.
Remove/replace references on sheet T-2 to California Fire Code.
Provide quantities of corrosives in batteries.
02/12/2014
02/27/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T14CM00818
8969 East Tanque Verde
Cell Antennas


TRANSMITTAL: February 20, 2014


COMMENTS: the following comments are relative to an application for a Special Exception relative to cell tower antenna modifications.


Provide the Special Exception decision letter. Demonstrate compliance, with the conditions stated in the letter, on the plans.
02/27/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/27/2014 GREGORY MCNEAL COMMUNICATIONS REVIEW Approved
03/18/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM00818
Antenna Equipment Replacement


1. Identify the electrical load of any proposed equipment, NEC 220.

2. Show the size of circuits used the power proposed equipment and identify any removed loads, NEC 225.


Ken Van Karsen
Elect Plan Review
PDSD, City of Tucson
520-837-4912
03/19/2014 MICHAEL ST. PAUL PLANNING-CITY HALL REVIEW Reqs Change See comments on Zoning.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2014 AROMERO4 OUT TO CUSTOMER Completed
04/11/2014 CPIERCE1 REJECT SHELF Completed