Permit Number: T14CM00816
Parcel: 140420190

Address:
2721 E ELVIRA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM00816
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/04/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/04/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The revised hot water piping design shows the new temperature mixing valve in an ASSE Standard 1069 configuration serving five lavatories and one shower. Five additional lavatories and one shower are being supplied with 140 degree Fahrenheit water with no mixing valves. Provide tempered water to all of the lavatories, provide scald-protection for all of the showers, and install any mixing valves per the manufacturer's recommendations. [Initial comment: Provide tempered water for the lavatories using approved devices conforming to ASSE Standard 1070. The temperature mixing valve shown in detail 1/P3.0 is ASSE Standard 1017 listed and, per the manufacturer, "[t]hey cannot be used by themselves for tempering water temperatures at fixtures where ASSE Standard 1016 or ASSE Standard 1070, listed devices are required." Reference: Sections 303.2, 416.5, and 607.1, IPC 2012.]