Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM00778
Parcel: 12106261C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00778
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/10/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.
2. Show that the system is able to reduce the ventilation flow rate to the minimum calculated using Section 403.3, IMC 2012. Reference: Section C403.2.5, IECC 2012.
02/10/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/10/2014 ROBERT SHERRY WATER REVIEW Approved
02/10/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/19/2014 SPOWELL1 WWM REVIEW Needs Review
02/19/2014 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/19/2014 JASON GREEN ENGINEERING REVIEW Approved
02/19/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
02/19/2014 MARTIN BROWN FIRE REVIEW Approved