| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/10/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/10/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012. 2. Show that the system is able to reduce the ventilation flow rate to the minimum calculated using Section 403.3, IMC 2012. Reference: Section C403.2.5, IECC 2012. |
| 02/10/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/10/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/10/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/19/2014 | SPOWELL1 | WWM | REVIEW | Needs Review | |
| 02/19/2014 | SPOWELL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/19/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/19/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/19/2014 | MARTIN BROWN | FIRE | REVIEW | Approved |