Permit Number: T14CM00745
Parcel: 117121260

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM00745
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2015 MARTIN BROWN FIRE REVIEW Reqs Change 1. Please provide Occupant load calculations that include the square footage of each area calculated.
2. Please identify all areas on the plans and their use. Example, what is going on in 125?
3. Please indicate the stairwell width and landing sizes
4. Please indicate where the fire sprinkler and fire alarm systems have been installed. If fire walls or barriers are used, please indicate their location on the plans and the details of how any openings are protected.
5. The Stamp for the Architect has expired
6. Please indicate the location of the egress lighting per IFC 1006
7. Are there CO2 tanks in the building?
8. Please provide a seating plan for the areas that have seating or tables.
9. Please indicate the type of exit signs used throughout
10. The plans indicate the exit width for the doors is 36 inches or greater, but per 1008.1.1, the measurement of the opening should be made with the door open at 90 degrees and to the stop. Is this what is actuallly onsite?
11. Why are the plumbing calcs and the occupant load calcs different?

Final Status

Task End Date Reviewer's Name Type of Review Description
03/11/2015 AROMERO4 OUT TO CUSTOMER Completed