Permit Number: T14CM00736
Parcel: 11904600L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00736
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2014 DAVID RIVERA ZONING REVIEW Approved
02/06/2014 LOREN MAKUS ENGINEERING REVIEW Approved
02/06/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS1; APPLICABLE CODES: CHANGE THE ACCESSIBILITY CODE TO THE 2009 ICC/ANSI A117.1.
2. SHEET A1.0; FLOOR PLAN: REMOVE THE EXIT SIGN DESIGNATION AT THE STOCK ROOM.
3. SHEET A1.1; ELEVATION A: LOCATE THE VERTICAL GRAB BAR FROM THE BACK WALL.
02/06/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/07/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
2. Show that the proposed replacement rooftop units meet the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2012.
4. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
02/07/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
02/07/2014 ROBERT SHERRY WATER REVIEW Approved
02/07/2014 MARTIN BROWN FIRE REVIEW Approved
02/07/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the scope of work for this activity. A note on the drawing states that the "plumbing piping is shown for reference and bidding purposes only. This project is for a shell building only." Is any plumbing work being done as part of this activity?
02/10/2014 SPOWELL1 WWM REVIEW Needs Review