Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM00735
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. STRUCTURAL: PROVIDE CALCULATIONS FOR THE NEW LINTEL DESIGN. |
| 02/06/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012. 2. Provide heating and cooling load calculations that justifies the capacity of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 3. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. |
| 02/06/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 02/06/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/06/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/06/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/06/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. |
| 02/07/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/07/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/26/2014 | FRODRIG2 | WWM | REVIEW | Completed |