Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM00735
Parcel: 13324010C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00735
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. STRUCTURAL: PROVIDE CALCULATIONS FOR THE NEW LINTEL DESIGN.
02/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012.
2. Provide heating and cooling load calculations that justifies the capacity of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
3. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
02/06/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
02/06/2014 ROBERT SHERRY WATER REVIEW Approved
02/06/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/06/2014 LOREN MAKUS ENGINEERING REVIEW Approved
02/06/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
02/07/2014 STEVE SHIELDS ZONING REVIEW Approved
02/07/2014 MARTIN BROWN FIRE REVIEW Approved
02/26/2014 FRODRIG2 WWM REVIEW Completed