Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM00681
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 02/04/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/04/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/04/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/05/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide heating and cooling load calculations that justify the total capacity of the heating and cooling equipment serving the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 2. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference: Section 302.1, IMC 2012. |
| 02/05/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 02/05/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/05/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/05/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/20/2014 | SPOWELL1 | WWM | REVIEW | Needs Review |