Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM00680
Parcel: 115211520

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00680
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2014 MARTIN BROWN FIRE REVIEW Approved DELETED DOORS MUST COMPLY WITH 2012 IFC, SECTION 504.2
02/21/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.2; EXIT PLAN: ARE THE NUMBERS (25) LISTED BELOW THE EXIT DESIGNATIONS A REFERENCE TO THE NUMBER OF OCCUPANTS EXITING AT THAT LOCATION? IF SO, THERE ARE 90 TOTAL OCCUPANTS PER SHEET A0. CLARIFY.
2. SHEET A1.2; PLAN KEYNOTES: NOTES 6 AND 37 WERE NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A2.2; DETAIL 2: INDICATE THE SIZE AND SPACING OF THE HORIZONTAL MEMBER AT THE BOTTOM OF THE EXISTING STRUCTURE. IN ADDITION, PROVIDE A CONNECTION TYPE.
4. SHEET A2.2; DETAIL 4: PROVIDE A DETAIL FOR THE CONNECTION OF THE VERTICAL METAL STUDS TO THE STRUCTURE ABOVE.
5. SHEET A2.2; DETAIL 6: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
6. SHEET A 3.1; DETAIL 3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
7. SHEET A5.1; ELEVATIONS 9 THROUGH 15: ARE THESE ELEVATIONS INDICATED ON A PLAN? VERIFY.
8. SHEETS A5.1 AND A5.2; KEYNOTES: ADD A NOTE INDICATING ALL KEYNOTES MAY NOT BE LOCATED ON THIS SHEET.
9. SHEETS A5.1 AND A5.2; KEYNOTES: NOTES 14, 15, 24, 25, 27, AND 28 WERE NOT LOCATED ON THESE SHEETS. VERIFY.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/24/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/26/2014 CPIERCE1 WWM REVIEW Completed
03/07/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/07/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
03/12/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the mechanical design as required to avoid using the corridor as a return air duct (HP-1, HP-3, and HP-5). Reference: Section 601.2, IMC 2012.
2. Provide balancing data for the exhaust grilles in restrooms 112 and 128. Reference: Section 403.7, IMC 2012.
3. Clarify the balancing data for HP-2 and HP-4; the sum of the outside air plus the return air appears to be significantly less than the supply air for each unit. Reference: Section 403.7, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/17/2014 CPIERCE1 REJECT SHELF Completed