Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM00647
Parcel: 12709016A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM00647
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2014 MARTIN BROWN FIRE REVIEW Approved
03/18/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/24/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
04/01/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The vents for the hydromechanical grease interceptor, P809, are still shown running horizontally below the flood rim of the hydromechanical grease interceptor. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012 (see also the definition, "horizontal pipe", Section 202, IPC 2012).]
2. Revise the gas piping shown on sheet P2.0 to agree with the revised gas riser diagram on sheet P5.0. The gas piping currently shown on sheet P2.0 is supplying gas to an existing heat pump. [Initial comment: Clarify the gas piping design. Unidentified appliance P808 is shown with a load of 380 CFH but the water heater, P800, with a load of 199 CFH is not shown. In addition, if Table 402.4 (1), IFGC 2012 has been used to size the pipe, the branch serving 380 CFH is undersized. Reference: Section 402.3, IFGC 2012.]
04/01/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Correct the ventilation calculations; see Sections 403.3.1 through 403.3.1.3, IMC 2012 for each zone and then use Section 403.3.2.1, IMC 2012 for RTU-4 and Sections 403.3.2.3.1 through 403.3.2.3.4, IMC 2012 for RTU-3. Base the occupant load on the appropriate occupancy classifications shown in Table 403.3, IMC 2012. [Initial comment: The occupant load used to calculate the required ventilation is not necessarily the same as the furniture layout provided by the Architect. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2012.]
2. Verify that the specified programmable thermostat (shown on sheet M1.0) provides an automatic start capability per Section C403.2.4.3.3, IECC. [Initial comment: Show that the proposed HVAC system meets the control requirements of Section C403.2.4 (e.g. show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap). Reference: Section C303.1, International Energy Conservation Code 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2014 CPIERCE1 REJECT SHELF Completed