Permit Number: T14CM00609
Parcel: 12218079B

Address:
1621 N DODGE BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM00609
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 3-14-14
Activity: T14CM00609 2nd review
Address: 1621 N Dodge Blvd
Applicant: Tucson Community Builders

INCLUSIVE HOME DESIGN:
Previous Comment:
Provide an accessible route from the public way with a no-step entrance, 1003.2. Vertical changes in floor elevation may not exceed ¼ inch (½ inch when beveled), 1003.4.
-Note- The elevation drawing or the site plan must show a ramped sidewalk if a paved driveway is not the accessible route.

FLOOR PLAN:
Previous Comments:
Doors between a garage and a residence shall be self-closing minimum 20-minute fire-rated, R302.5.1.
Attached garages require at least one GFCI receptacle, E3901.9, E3902.2.
-Note- Parking structures must be open on two or more sides to be considered a carport.

PLUMBING PLAN:
Previous Comment:
All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Provide gray water segregation for at least one (1) bathing fixture or clothes washing machine for all single story buildings.
-Note- Kitchen sinks may not share a gray water drain line. Clarify the parallel 4" building sewers indicated on the riser diagrams. The extensive layout proposed exceeds the minimum criteria of the ordinance however. Two drain discharge lines from the clothes washing machine would suffice. One of these would need to discharge above grade with a cap through an exterior wall. The other would connect to a normal DWV layout.

Previous Comment:
All construction drawings submitted after March 1, 2009 for one- or two-family dwellings require a solar water heating system, or future installation preparation with one of the following provisions: control and ¾"water piping; 3" metallic sleeve; or an accessible attic over the water heater.
-Note- If water piping is installed to meet this requirement a control conduit must accompany them.

MECHANICAL PLAN:
Previous Comment: Provide a mechanical plan layout with duct sizes consistent with the calculations provided, M1401.3.
-Note- The mechanical plan provide may not be approved if it is sized differently than the calculations provided.

Previous Comment: Specify on the mechanical plan the equipment to be installed per calculations provided.
-Note- The calculations required are not intended to be field references for the mechanical system. Provide a mechanical equipment list on the mechanical plan.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2014 CPIERCE1 REJECT SHELF Completed