Permit Number: T14CM00609
Parcel: 12218079B

Address:
1621 N DODGE BL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM00609
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 2-28-14
Activity: T14CM00609
Address: 1621 N Dodge Blvd
Applicant: Tucson Community Builders

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

INCLUSIVE HOME DESIGN:
1. Provide a complete set of notes on the plan to meet the Inclusive Home Design Ordinance 10463.
2. Provide an accessible route from the public way with a no-step entrance, 1003.2. Vertical changes in floor elevation may not exceed ¼ inch (½ inch when beveled), 1003.4.

FLOOR PLAN:
3. Doors between a garage and a residence shall be self-closing minimum 20-minute fire-rated, R302.5.1.

PLUMBING PLAN:
4. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Provide gray water segregation for at least one (1) bathing fixture or clothes washing machine for all single story buildings.
5. All construction drawings submitted after March 1, 2009 for one- or two-family dwellings require a solar water heating system, or future installation preparation with one of the following provisions: control and ¾"water piping; 3" metallic sleeve; or an accessible attic over the water heater.

MECHANICAL PLAN:
6. Provide a mechanical plan layout with duct sizes consistent with the calculations provided, M1401.3..
7. Specify on the mechanical plan the equipment to be installed per calculations provided.

ELECTRICAL PLAN:
8. At least one wall switch controlled light must be provided in attached garages, E3903.3.
9. Attached garages require at least one GFCI receptacle, E3901.9, E3902.2.

OUTDOOR LIGHTING CODE
10. Include all exterior lighting proposed in the outdoor lighting calculation.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2014 CPIERCE1 OUT TO CUSTOMER Completed
03/03/2014 CPIERCE1 REJECT SHELF Completed