Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM00575
Parcel: 13327001C

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM00575
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2014 MARTIN BROWN FIRE REVIEW Denied Code analysis information on cover sheet incorrect. A restaurant is an "A-2" occupancy, not mercantile. Occupant load 100 or greater for an A-2 occupancy requires fire sprinklers. Sprinklers will be monitored. Sprinklers and monitoring are separate, deferred submittals. Please include this information on code analysis section.
02/06/2014 DAVID RIVERA ZONING REVIEW Approved
02/11/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET T1.1
1. Correct the electrical code to the 2011 NATIONAL ELECTRICAL CODE.
2. At the Occupancy Classification add to RESTAURANT, the 2012 IBC Occupancy Classification of "A2".
3. Change "MERCHANTILE" to "RESTAURANT A2".
4. Reevaluate your assembly load of 10 for ASSEMBLY W/O FIXED both Indoor and outdoor. There is no such allocation. Please reference Table 1004.1.2 for assembly load allowances.
5. Recalculate your total occupancy load as per Table 1104.2.1.
END OF REVIEW
02/18/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing plan and the civil grading & paving plan with respect to the first floor elevation, the rim elevation of the next upstream sewer cleanout, and the inverts of the cleanouts for the grease waste and the building drain.
2. Provide hydraulic calculations to justify the size of the roof scupper. Show how overflow protection is being provided. Clarify the design of the collector box shown in detail 5.A3.1. Reference: Sections 1106 and 1108.3, IPC 2012.
02/18/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist.
02/18/2014 ROBERT SHERRY WATER REVIEW Approved
02/26/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2014 CPIERCE1 REJECT SHELF Completed