Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM00541
Parcel: 117200270

Review Status: Completed

Review Details: REVISION - - 7TH

Permit Number - T14CM00541
Review Name: REVISION - - 7TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. For all the handrails located in the middle of the steps and ending in the middle of the forth tread from the bottom of the landing and aisle adjacent to the arena, extend the hand rail to the face of the second riser from the bottom. Reference attached suggested sketch over lay at detail 9/R27.1. Confirm structural stability of extension and modify as required for safety.
a. Please provide a large scale detail of this extension and make reference from sheet R27.0.
2. At detail 5/R27.1 the wall mounted handrail at the top of the landing is non-compliant. The 2'-10" is to be from the top landing surface to the top of the handrail. Please provide the handrail extension at the same angle to an appropriate point of termination.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2015 AROMERO4 APPROVAL SHELF Completed
05/08/2015 AROMERO4 OUT TO CUSTOMER Completed