Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM00522
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 03/13/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/24/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | If AC1.5 is being operated as supplemental cooling under exception 2 of Section C403.2.2, IECC 2012, provide the sequence of operation for the AC unit. [Initial comment: Provide justification for installing HVAC units having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations (187.4 MBH calculated vs. 242.2 MBH provided). Reference: Section C403.2.2, IECC 2012.] |
| 03/24/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The responsibility schedule on sheet T1.0 indicates that the gas piping to the tenant space will be done under this activity. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 107.2.1, IBC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/27/2014 | AROMERO4 | APPROVAL SHELF | Completed |
| 03/27/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 03/27/2014 | GERARDO BONILLA | REJECT SHELF | Completed |