Permit Number: T14CM00522
Parcel: 10409002D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM00522
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
03/13/2014 MARTIN BROWN FIRE REVIEW Approved
03/24/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied If AC1.5 is being operated as supplemental cooling under exception 2 of Section C403.2.2, IECC 2012, provide the sequence of operation for the AC unit. [Initial comment: Provide justification for installing HVAC units having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations (187.4 MBH calculated vs. 242.2 MBH provided). Reference: Section C403.2.2, IECC 2012.]
03/24/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The responsibility schedule on sheet T1.0 indicates that the gas piping to the tenant space will be done under this activity. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 107.2.1, IBC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/27/2014 AROMERO4 APPROVAL SHELF Completed
03/27/2014 AROMERO4 OUT TO CUSTOMER Completed
03/27/2014 GERARDO BONILLA REJECT SHELF Completed