Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM00522
Parcel: 10409002D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00522
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2014 CPIERCE1 WWM REVIEW Completed
02/03/2014 JASON GREEN ENGINEERING REVIEW Approved
02/03/2014 KEN BROUILLETTE FIRE REVIEW Denied NEED EMERGENCY LIGHTING IN THE SALES FLOOR AREA-NOT SHOWN ON SHEET A2.0
02/04/2014 STEVE SHIELDS ZONING REVIEW Approved
02/05/2014 ROBERT SHERRY WATER REVIEW Approved
02/05/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide specifications and installation details for all appliances that will be connected to the plumbing system as part of this activity (e.g. the water softener, the boiler, the water bottler, etc.). If the appliances are not to be installed as part of this activity, they shall be noted as being for "future installation under a separate permit." Reference: Section 107.2.1, IBC 2012.
2. Lined water heaters with a heat input of 200,000 BTU per hour or more, an operating water temperature of 210ยบ F or greater, and a nominal water containing capacity of 120 gallons or more are required to comply with the rules contained in Article 4 (Arizona Boilers and Lined Hot Water Heaters) of the Arizona Administrative Code. http://www.azsos.gov/public_services/Title_20/20-05.htm#ARTICLE_4.
3. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
4. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Per the manufacturer of the temperature mixing valve shown in detail 2/P1.0, "When used in an ASSE 1017 application at the hot water source, the Watts Thermostatic Mixing Valve Series MMV cannot be used by itself to control final temperature at fixtures where ASSE Standard 1016-96 or ASSE Standard 1070 listed devices are required." Reference: Sections 303.2 and 416.5, IPC 2012.
5. Revise the water heater installation detail (4/P1.0) to show the thermal expansion tank. Reference: Section 607.3, IPC 2012.
6. Show that the proposed reduced pressure zone backflow prevention assemblies (for the water distribution system connection and for the boiler connection) will be installed in accessible, non-concealed locations per the manufacturer's installation instructions. The air gap and drain line from each reduced pressure zone backflow prevention assembly shall be piped from the relief valve connection to a clearly visible discharge location that will prevent the occurrence of water damage. Reference: Section 608.14, IPC 2012.
7. Coordinate the termination point of the T&P relief valve as described in the plumbing fixture schedule and detail 4/P1.0 with detail 2/P1.0; floor drains in a restroom shall not be used as indirect waste receptors. Reference: Section 802.3, IPC 2012.
02/05/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide justification for installing HVAC units having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations (187.4 MBH calculated vs. 242.2 MBH provided). Reference: Section C403.2.2, IECC 2012.
2. According to the submitted mechanical compliance certificate, the mechanical systems will be required to "meet the commissioning and completion requirements in Section C408.2." If commissioning is desired, provide a copy of the commissioning plan with the next submittal. Reference: Section C408.2.1, IECC 2012.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2012.
4. Condensate drains for the rooftop units shall be terminated at an approved disposal location. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
5. Revise the sequence of operation for the restroom exhaust fan (EF-1) so that when the building is occupied, all of the air supplied to the restrooms will be exhausted. The use of occupancy sensors to control the fan will result in air supplied to the restrooms not being exhausted when the restrooms are unoccupied. Reference: Section 403.2.1 (4), IMC 2012.
6. The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2012 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012; for HVAC systems serving multiple zones (e.g. AC1-2), see Section 403.3.2.3, IMC 2012.
7. Verify the zone areas used to calculate the minimum ventilation requirements. Reference: Sections 202 (Net Occupiable Floor Area) and 403.2, IMC 2012 and footnote a, Table 403.3, IMC 2012. See also Section C403.2.5, IECC 2012.
02/20/2014 GERARDO BONILLAS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/26/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the sequence of operation for the restroom exhaust fan (EF-1) so that when the building is occupied, all of the air supplied to the restrooms will be exhausted. The use of occupancy sensors to control the fan will result in air supplied to the restrooms not being exhausted when the restrooms are unoccupied. Reference: Section 403.2.1 (4), IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2014 CPIERCE1 OUT TO CUSTOMER Completed
03/10/2014 CPIERCE1 REJECT SHELF Completed