03/05/2014 RAFAEL CANCINO BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS

Date: March 5, 2014
Activity: T14CM00466
Address: 2309 E. 8th St.
Applicant: Mr. Jesus Leyva


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the code references on the plans.

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Adopted 2012 codes are listed at the Planning & Development Services web site. Show the code references used for the design.
" PROVIDE SECOND COPY OF PLANS


FRAMING PLAN:

1. Provide structural calculations for new trusses and/or identify on plans that trusses will be manufactured by state approved manufacturer and calculations will be submitted at a later date.
2. Specify nailing schedule for brace wall panels. (Details 3 and 4)
3. Detail 3, stucco is not allowed to touch existing grade. Adjust to meet code requirements. R703.6
4. Provide weep screed at bottom of plaster.

PLUMBING PLAN:

1. On the fixture schedule account for all fixtures including existing fixtures.

MECHANICAL PLAN:

1. Provide size of existing HVAC unit.

ELECTRICAL PLAN:

1. Ensure smoke detectors are installed in existing bedrooms.