Review Details: RESUBMITTAL
Permit Number - T14CM00293
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The hot water supply to the lavatory in this suite is still served by an instantaneous water heater that does not limit the temperature of the hot water to no more than 110 degrees Fahrenheit (see detail 11/P3.0 and Plan C/P2.0). [Initial comment: Show how the temperature of the hot water supply to the public lavatory is to be controlled. The instantaneous water heater specified for the lavatory is not capable of controlling the temperature of the water delivered to the lavatory. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.] |
| 02/14/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/14/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Detail 6/P3.0 still shows the condensate terminating over a splash block on the roof. Coordinate the mechanical and plumbing sheets. [Initial comment: Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage. Terminating the condensate drain of a rooftop unit (e.g. detail 6/P3.0) is not acceptable. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/19/2014 | AROMERO4 | APPROVAL SHELF | Completed |
| 02/19/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 02/19/2014 | GERARDO BONILLA | REJECT SHELF | Completed |