Permit Number: T14CM00293
Parcel: 12006058B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00293
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2014 MARTIN BROWN FIRE REVIEW Approved
01/24/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/27/2014 ROBERT SHERRY WATER REVIEW Denied Clarify the intent of the modifications to the water service for Suite 105. Keynote # 4 on C/P2.0 indicates that a new "1" water meter and a 1-1/4" backflow preventer" will be installed to serve the new restroom. Is this new water meter intended to be a sub-meter for the future tenant or a replacement of the existing meter supplied by Tucson Water? If not a sub-meter, all water meters for Tucson Water shall be located at the property line at a location accessible to Tucson Water. Show the location and size of the existing water service meter and backflow device on the site plan.
01/27/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Backflow preventers are required to be located in accessible locations and per the manufacturer's installation instructions; a location above a ceiling is not accessible. Reference: Section 608.14, IPC 2012.
2. Show how the temperature of the hot water supply to the public lavatory is to be controlled. The instantaneous water heater specified for the lavatory is not capable of controlling the temperature of the water delivered to the lavatory. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.
01/27/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage. Terminating the condensate drain of a rooftop unit (e.g. detail 6/P3.0) is not acceptable. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson
02/03/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2014 SHANAE POWELL OUT TO CUSTOMER Completed
02/11/2014 CPIERCE1 REJECT SHELF Completed