Permit Number: T14CM00276
Parcel: 12006058B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM00276
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Exhaust fan EF-3 is located less than 10-feet from a roof edge; provide a guard per Section 304.11, IMC 2012 or relocate the exhaust fan. [Initial comment: Provide guards for equipment located within 10 feet of a roof edge (e.g. exhaust fans or condensing units located within ten feet of the east edge of the roof). Reference: Section 304.11, IMC 2012.]
2. Detail 6/P3.0 still shows the condensate terminating over a splash block on the roof. Coordinate the mechanical and plumbing sheets. [Initial comment: Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage. Terminating the condensate drain of a rooftop unit (e.g. detail 6/P3.0) is not acceptable. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.]
02/14/2014 ROBERT SHERRY WATER REVIEW Approved
02/14/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved