Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T14CM00205
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2014 LHANLY1 NPPO REVIEW Passed
01/13/2014 LEE HANLY BUILDING-RESIDENTIAL REVIEW Approved 1) Addition requires a 1 hour rated exterior wall at lot line. This may be accomplished by using plaster on the exterior, or by adding a layer of type x or type c sheetrock to the exterior side of the indicated frame wall.

2) Provide suitable hold-downs to resist the overturning force of this addition.

3) Addition must meet criteria for a "free-standing" structure, or you must provide engineering for the attachment to the existing mobile home. Providing a detail for the use of a drag-strut at the opening to the mobile home may meet the requirement.

Provide written responses and the requested details for the corrections noted above. If further assistance is required you may make an appointment to discuss some methods that may be used to make this addition code compliant.
03/05/2014 STEVE SHIELDS ZONING REVIEW Approved
03/05/2014 JASON GREEN ENGINEERING REVIEW Approved