Permit Number: T14CM00192
Parcel: 13419042A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM00192
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2014 MARTIN BROWN FIRE REVIEW Approved
04/01/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage (the entire area appears to be covered with either concrete or asphalt paving). Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. The 10" x 10" intake vent is not located on an exterior wall; show how outside air is to be introduced into the space.
3. Correct the room area used for the ventilation calculations (it is 320 SF, not 210 SF). If the A/C units are operating in a lead/lag situation, clarify how 100 CFM of outside air is being supplied to the room.
4. Locate key note #7 on the plans. (Will dampers also be installed on the A/C units to seal the room when the fire suppression system is activated?)

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2014 SHANAE POWELL REJECT SHELF Completed