Permit Number: T14CM00192
Parcel: 13419042A

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T14CM00192
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Reqs Change 1) STRUCTURAL ADDENDUM SHEETS MP-1, MP-2 DO NOT COMPLY WITH CITY OF TUCSON MINIMUM FONT SIZE OF 3/32". THESE SHEETS ARE TO BE INCLUDED IN THE PRIMARY PLAN SET, AND ARE TO MEET MINIMUM FONT SIZES.

2) MECHANICAL SHEET M-1 REFERENCES THE CITY OF PHOENIX CODE AMENDMENTS IN THE "CODE INFORMATION" BOX. EITHER DELETE REFERENCE OR ALTER NOTATION FOR "CITY OF TUCSON".
01/13/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
01/15/2014 KEN BROUILLETTE FIRE REVIEW Approved
01/17/2014 MICHAEL ST. PAUL ZONING REVIEW Approv-Cond Planning approval is required.

Email address are required with the consultants' information on the cover sheet.
01/31/2014 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved Waiver provided.
03/10/2014 CPIERCE1 COMMUNICATIONS REVIEW Approved PER JEFFREY SELIGMAN

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
03/19/2014 CPIERCE1 REJECT SHELF Completed