Permit Number: T14CM00148
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00148
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2014 MARTIN BROWN FIRE REVIEW Approved
01/14/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/14/2014 ROBERT SHERRY WATER REVIEW Approved
01/14/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the mechanical and electrical plans. The electrical plans show one split system serving the storage room compared to the two systems shown on the mechanical plans.
2. Verify that the two outside air intakes are positioned on an exterior wall and that the openings comply with the requirements of Section 401.4, IMC 2012.
3. Provide cooling load calculations that justify the capacities of the cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
4. The ventilation calculations indicate that the minimum flow rate for outside air is 78 CFM but the design flow rate for outside air is 105 CFM. Show how the HVAC controls are capable of reducing the outside air to the minimum flow rates required by Chapter 4, IMC 2012. Reference: Section C403.2.5, IECC 2012.
01/17/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G-0001; PROJECT DATA: REVISE THE 'TYPE OF USE' TO F-1 (FOOD PROCESSING) AND S-2 (LOW HAZARD STORAGE).
2. SHEETS I-1102 AND I-1103: PROVIDE A NORTH ARROW ON ALL PLANS.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/29/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approv-Cond MECHANICAL PLANS SHOW 2 SPLIT SYSTEMS WHILE ELECTRICAL ONLY HAS ONE. THIS APPROVAL IS ON ASSUMPTION THAT MECH DESGINER WILL DELETE ONE OF THE SYSTEMS AS UNNECESSARY.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
02/03/2014 CPIERCE1 REJECT SHELF Completed