Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM00137
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/09/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/15/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012. 2. Revise the proposed installation of the temperature mixing valve to comply with the manufacturer's listing (i.e. the specified valve is a point-of-use device, designed to serve a single outlet; see detail 2/P5001). Reference: Section 303.2, IPC 2012. 3. Appliances (e.g. coffee brewers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 4. Provide a detail showing how the island vents are to be constructed. Reference: Section 916, IPC 2012. 5. Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. Reference: Section 1003.1, IPC 2012. |
01/15/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/15/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
01/17/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET G-0001; PROJECT DATA: REVISE THE 'TYPE OF USE' TO F-1 (FOOD PROCESSING) AND S-2 (LOW HAZARD STORAGE). 2. SHEET G-0001; PROJECT DATA: REVISE THE 'TYPE OF OCCUPANCY' ON THE KIOSK TO F-1. 3. SHEET G-0011; SPECIFICATIONS: ARE THE REQUIREMENTS OF THE IBC SECTION 402.6.2 FOR THE KIOSK IN THESE SPECIFICATIONS? ADDRESS EACH ITEM IN 402.6.2 SPECIFICALLY. THE HORIZONTAL SEPARATION LISTED IN SECTION 402.6.2(3) IS WAIVED FOR THE ESCALATOR PER THE BUILDING OFFICIAL. 4. SHEET A-1104: PROVIDE A NORTH ARROW ON THE PLAN. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
01/29/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/03/2014 | CPIERCE1 | REJECT SHELF | Completed |