Permit Number: T14CM00090
Parcel: 124082240

Address:
50 N MOUNTAIN AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM00090
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2014 JASON GREEN ENGINEERING REVIEW Approved
10/06/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify how the mop sink in the laundry room is to be vented. Reference: Section 901.2.1, IPC 2012. [Initial comment: The fixture branch or stack for a standpipe and fixture drain serving an automatic clothes washer shall be at least 3" in diameter. Reference: Section 406.2, IPC 2012.]
2. Correct the label for the cleanout located at the south end of the building drain: it cannot be a two-way cleanout. [Initial comment: An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow (i.e. one-way cleanouts). Reference: Sections 708.3.5 and 708.5, IPC 2012.]
10/08/2014 MARTIN BROWN FIRE REVIEW Passed THIS PERMIT HAS BEEN CHANGED TO A FOUNDATION AND PLUMBING ONLY-FIRE WILL NOT REVIEW. CONSTRUCTION OF A BUILDING IS NOT APPROVED FROM FIRE AT THIS TIME.
10/15/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide appropriate cover sheet:
a. Show proper title for construction of foundation and plumbing only
b. Provide proper sheet index
c. Include building code analysis
2. Provide 2 sets of Structural Calculations for foundation only.
END OF REVIEW
10/20/2014 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2014 CPIERCE1 REJECT SHELF Completed