Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM00085
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 02/24/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/24/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | The existing water distribution system is basd upon the Uniform Plumbing Code. Per the 2012 UPC, the existing 2" watr meter is serving 154 fixture units in a flush-valve system. The demand is 81 GPM wwhich will result in a water velocity of 7.7 fps in the existing 2" schedule 40 PVC water sevice pipe. |
| 02/24/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 02/24/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/25/2014 | FRODRIG2 | WWM | REVIEW | Completed |