Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM00085
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/06/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 01/07/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide information to show compliance with International Energy Conservation Code section 405 |
| 01/07/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to verify the ventilation complies with Section 403.3, IMC 2012 for the proposed occupancy. |
| 01/07/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Specify on cover sheet that you are arriving at your increased occupant load per section 1004.2 of the IBC. Provide plumbing fixture calculations using the increased occupant load figures. I'm counting 5 exits, pp T1 is indicating 3 |
| 01/07/2014 | ROBERT SHERRY | WATER | REVIEW | Denied | Verify the size of the existing water meter (or meters) and backflow preventer (preventers) serving these two suites and the total demand for the suites. |
| 01/07/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide calculations to show that sufficient plumbing fixtures are available for the proposed number of occupants. |
| 01/07/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 01/07/2014 | LHANLY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/24/2014 | SPOWELL1 | WWM | REVIEW | Needs Review |