Permit Number: T14CM00085
Parcel: 14029037B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM00085
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2014 STEVE SHIELDS ZONING REVIEW Approved
01/06/2014 LOREN MAKUS ENGINEERING REVIEW Approved
01/07/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide information to show compliance with International Energy Conservation Code section 405
01/07/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to verify the ventilation complies with Section 403.3, IMC 2012 for the proposed occupancy.
01/07/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Reqs Change Specify on cover sheet that you are arriving at your increased occupant load per section 1004.2 of the IBC.

Provide plumbing fixture calculations using the increased occupant load figures.

I'm counting 5 exits, pp T1 is indicating 3
01/07/2014 ROBERT SHERRY WATER REVIEW Denied Verify the size of the existing water meter (or meters) and backflow preventer (preventers) serving these two suites and the total demand for the suites.
01/07/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide calculations to show that sufficient plumbing fixtures are available for the proposed number of occupants.
01/07/2014 KEN BROUILLETTE FIRE REVIEW Approved
01/07/2014 LHANLY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/24/2014 SPOWELL1 WWM REVIEW Needs Review