Review Details: COMMERCIAL - TI
Permit Number - T14CM00077
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/06/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 01/07/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/07/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide the structural calculations for the equipment platforms and the curbs for the rooftop units. |
| 01/07/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Provide structural information to show that roof will support all the "future" equipment indicated. |
| 01/07/2014 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the water meter serving this activity. |
| 01/07/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide the site plan referenced in keynote P on sheet P1 (i.e. what is the source of the 4" CW). |
| 01/07/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 01/07/2014 | LHANLY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/15/2014 | SPOWELL1 | WWM | REVIEW | Needs Review |